Open Access
Issue
Int. J. Simul. Multidisci. Des. Optim.
Volume 9, 2018
Article Number A1
Number of page(s) 7
DOI https://doi.org/10.1051/smdo/2017008
Published online 13 March 2018

© C.M. Lamin and A.K. Singh, published by EDP Sciences, 2018

Licence Creative CommonsThis is an Open Access article distributed under the terms of the Creative Commons Attribution License (http://creativecommons.org/licenses/by/4.0), which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.

1 Introduction

The need for energy goes on increasing day by day but the supply of energy is very limited. The main reason for the energy crisis is that we have not able to harvest all the available energy in the nature due to technical generation problem or we can say we have not get enough ideas how to generate energy for our needs and consumptions [1]. Power losses appear in every part of our power system like in generation, transmission and distribution as well as in consumption process. Starting from the generation, the inputs such as petroleum, natural gas and coal in case of thermal power plant; nuclear fuel as in case of nuclear power plant were combusted to produce heat to convert water into steam to run the prime mover of the generators. In the process of combustion a large amount of energy is lost in the form of heat. Even in the case of hydropower plant there is a loss in the transformation process due to technical inefficiency. After generation; electricity output is transmitted using transmission lines usually high or medium voltage above 132 kV. In transmission lines the main causes of electricity loss are the technical factors, the climatological factors and the geographical conditions. Corona loss also occurs when the line to line voltage exceed the disruptive critical voltage i.e. the potential difference between the conductors, at which the electric field intensity at the surface of the conductor exceed the critical value [2]. Radiation loss occurs when the magnetic lines of force about a conductor do not return to the conductor when the cycle alternates. High frequency radiations like X-rays, gamma rays, ultraviolet rays called ionizing radiations can remove an electron from an atom or molecule. Low frequency radiations are called as non ionizing radiation and they have enough energy to move an atom in a molecule [3]. In case of distribution losses the main causes are both technical and non technical factors [4,5]. This is because in distribution, besides transportation, there are several operations like tapings, metering and controls. These operations consumed energy which results into power loss.

2 Line flows

In order to find the loss in each branch i.e. from one bus to the other bus we need to calculate the line flows from one branch to the other in both directions. The line flows equation is given as follow [6]:

The power flow at bus p from bus p to bus q is given as Ipq=(VpVq)Ypq+VpY2,(1) Now, PpqjQpq=VpIpq*, =Vp[(Vp*Vq*)]Ypq*+Vp*Y2,(2) Or,PpqjQpq=Vp(Vp*Vq*)Ypq*+VpVp*Y2(3) Here Ppq is the real power flow from bus p to q and Qpq is the reactive power flow from q to p.

Similarly, at bus q the power flow from bus q to p is given as: PqpjQqp=Vq(Vq*Vp*)Yqp*+VqVq*Y*2,(4) The total power loss,PTLoss=PqpjQqpp=1,2,,n q=1,2,,n.(5)

2.1 Admittance matrix

To convert impedance into admittance we used the following formula: Admittance,(Ypq)=1impedance,Zpq,(6) where, p and q are bus number = 1, 2,…, n Admittance matrix[Y]=[ Y11Y12Y1n Y21Y22Y1n ... ... Yn1Yn2Ynn].(7)

3 Distributed generators

Distributed generation (DG) is a small-scale generation which is not directly connected to main transmission system and is not centrally dispatched [7]. It can be of great advantage in isolated locations where central generation is a challenge and where grid extension is difficult. It can be fed back into the grid in an integrated way [8].

The available size of DG per module can be as little as 1 kW to as high as 250 MW. Depending on the technology size, DGs may be classified into [9]:

  • micro (1 W–5 kW);

  • small (5 kW–5 MW);

  • medium (5–50 MW);

  • large (50–300 MW).

Based on their electrical output characteristics distributed generators can be classified into three classes of DG technologies are as follows [10]:

  • synchronous generator technologies (SGTs);

  • induction generator technologies (IGTs);

  • asynchronous generator based technologies (AGTs).

SGTs can maintain their terminal voltage by varying the amount of reactive power they generate. So they are able to operate at varying power factors [11].

IGTs required reactive power to magnetize their rotors and this can be supplied either by the grid or capacitor banks [11].

AGTs use power electronic devices as interface to the grid. Power electronic devices invert DC power generated to AC power at the required grid frequency and voltage [11].

3.1 Synchronous generator technologies (SGTs)

SGTs are modeled as generators with constant terminal voltage with known real power generation and known reactive power limits. A constant terminal voltage could be achieved by varying the reactive power generated. This model incorporates the variable power factor model of Gonzalez-Longatt (2007) and constant voltage model of Teng (2007). For a given real power (PSGT) and terminal voltage (VSGT) the reactive power (QSGT) was allowed to vary as [11]: 0.75PSGTQSGT0.75PSGT.(8)

When SGT is implement on a network the PQ bus where the SGT is to be connected gets converted to a PV bus. If Pli is the real power consumed by the load at bus i and Qli is the reactive power consumed by the load at the same bus, on connecting the synchronous generator technology, the new real power (Pnli) and new reactive power (Qnli) consumed at bus i can be determined by [11]: Pnli=PliPSGT,(9) Qnli=QliQSGT.(10)

3.2 Induction generator technologies (IGTs)

In IGT the reactive power absorbed from the grid can be derived from the equivalent circuit of an induction generator as follows [11]: Q=V2XcXmXcXm+XV2+2RP2(R2+X2)X(V2+2RP)24P2(R2+X2)2(R2+X2),(11) where, Xm is the magnetizing reactance; Xc is capacitor banks reactance; X is the sum of the rotor and stator leakage reactance; R is the sum of the rotor and stator resistances; V is the voltage; P is the real power generated and it is positive when it is injected into the grid.

By considering only the first two derivatives of the McLaurin approximation of equation (11) and neglecting resistance R, then the reactive power absorbed by an IGT can be approximated as: Q=Q0Q1*PQ2*P2.(12)

Hence, for a given generated real power, P and machine parameters, Xc, Xm, and X, the reactive power consumed by the induction based generator technologies can be obtained as: QIGTV2XcXmXcxm+XV2P2.(13)

On implementation of IGT the voltage at PQ buses are unknown until convergence of a load flow algorithm. So equation (9) cannot be used in a straight forward manner to determine the reactive power consumed at the PQ Bus. The reactive power consumed by the induction generator can be determined as follow [11]:

  • the load flow of the test network with no IGT connected is determined;

  • the voltage obtained at the bus where the generator is to be connected is used in solving equation (9);

  • new active power (Pnli) and new reactive power (Qnli) are determined from the pre-determined P and calculated QIGT in equation (9) as follows:

Pnli=PliPIGT,(14) Qnli=QliQIGT.(15)

3.3 Asynchronous generator based technologies (AGTs)

In AGT by varying the triggering angles for the power electronic interfaces of AGT, it can be made to operate at varying power factors. For a given generated real power (PAGT) and power factor (cos ϕ) the reactive power generated is given as [11]: QAGT=±PAGT2(1(cosφ)21),(16) If cos ϕ ≥ 0, QAGT ≥ 0. Otherwise, QAGT< 0.

When connect to a network, AGT is modeled as a negative loads. If Pli is the real power consumed by the load at bus i and Qli is the reactive power consumed by the load at the same bus, on connecting the asynchronous generator technology, the new real power (Pnli) and reactive power (Qnli) consumed at bus i can be written as: Pnli=PliPAGT,(17) Qnli=QliQAGT.(18)

3.4 Penetration level

Penetration level (PL) refers to how much of the real power demand of the network is met by the DG technologies. It can be mathematically represented as [11]: PL=PDGPload×100%,(19) PL of 0% represents that the load demand is totally met by the grid and a PL of 100% means that the load demand is supplied entirely by the DG Technologies. PDG is the output of the DGs.

4 Problem formulation

The aim of the proposed work is to calculate and reduce transmission power loss by using DG technology.

thumbnail Fig. 2

Single line diagram of the system parameters after implementation of DG.

4.1 Algorithm followed for loss reduction using DG:

  • Step 1

    : Read the input data.

    • Line data (impedance, shunt reactance) [Appendix A].

    • Bus data (voltage, active and reactive load) [Part 5].

  • Step 2

    : Calculate the admittance matrix of the system [Eqs. (6), (7)].

  • Step 3

    : Calculate power loss by Gauss-Seidel iteration method [Eq. (3)].

  • Step 4

    : Simulate the network in PSSE.

  • Step 5

    : Implement DGs at bus 2 and bus 3 [Fig. 2].

  • Step 6

    : Input the PL [Appendix A].

  • Step 7

    : Input the ratings of distributed generators [Appendix A].

  • Step 8

    : Calculate their per unit impedance.

  • Step 9

    : Calculate the new admittance matrix [Eqs. (6), (7)].

  • Step 10

    : Calculate power loss by Gauss-Seidel iteration method [Eq. (5)].

  • Step 11

    : Compare the losses with and without distributed generators.

    • If the losses are less than without distributed generators, then simulate with PSEE. And stop.

    • If the losses are more than without distributed generators or not economical compare to distributed generator size, PL is changed. And step 6 is repeated.

  • Step 12

    : Calculate the overall reduction of losses considering the DGs rating.

  • Step 13

    : Integrate the selected DGs size to the network and simulate using PSSE under the selected PL.

  • Step 14

    : Calculate the loss reduction percentage.

5 System under study

Power grid Corporation of India Ltd. Nirjuli was commission on 2nd June 1991. The transformation capacity of this Sub-Station is 100 MVA. There are 2 power transformers each of 50 MVA transformation capacities. It draws the power from Ranganadi hydro electric power plant (RHEP), through 132 kV transmission line and also from Gohpur substation through Gohpur-ltanagar transmission. There are 3 generators at RHEP bus each with a generating power of 135 MW. There are three outgoing 33 kV feeder namely, 33 kV AP Feeder-1 for Itanagar, 33 kV AP Feeder-2 for Banderdewa and 33 kV AP Feeder-3 for Nirjuli. The total load is around 29 MW and 21.58 MVAR after the transformation process and the Gohpur bus take around 40 MW and 29.76 MVAR when RHEP line is in good condition. The maximum load through the Power grid Corporation of India ltd. Substation, Nirjuli is 85 MW and around 320 MW are dispatched to other substations e.g. Chimpu and Lekur through nahalagun-dikrong transmission line (NDTL). Figure 1 shows single line diagram of the actual parameter of the system, the value of which is shown in the Appendix A. The value of the system parameters are converted into per unit impedance and admittance with the base of 150 MVA, 132 kV and 33 kV [6,12].

The network busses are numbered as follows:

  • main substation bus as slack bus (Bus 1);

  • 33 kV Nirjuli bus (Bus 2);

  • Gohpur bus (Bus 3);

  • RHEP bus (Bus 4);

  • NDTL bus (Bus 5).

After calculation we adopted a DG PL of 10%, which is found economical, at bus 2 and bus 3 and the size of distributed generators is 5 MVA each. Distributed generator at bus 2 is taken to be a hydro power plant [13] which is a synchronous model type and distributed generator at bus 3 is taken to be a thermo-photovoltaic power plant [14,15] which is an asynchronous model type. Figure 2 shows the parameter of the modified system after implementation of DG technology, the rating and impedance of which is shown in Appendix A.

thumbnail Fig. 1

Single line diagram of actual parameter of the network without DG.

6 Results and outputs

7 Conclusion

Using Gauss-Seidel method, the real power loss in the system is 1.92 MW and the reactive power loss is 90.09 MVAR (Tab. 1) which amount 90.10 MVA. After the implementation of DG the real power loss is found to be 2.77 MW and the reactive power loss is 37.55 MVAR (Tab. 1), the magnitude of losses is 37.65 MVA. The reduction in power loss is 58.21%. Although there is a bit increase in real power loss, the overall loss decreased significantly.

From the output of PSSE simulation software, the real power loss of the system is 4.7 MW and the reactive power loss is 172.7 MVAR (Tab. 2) which amount 172.76 MVA. After the implementation of DG technology, the real power loss is 4.4 MW and the reactive loss is 150.9 MVAR (Tab. 3), the magnitude of losses is 150.96 MVA. There is 12.61% reduction in power loss.

We obtained a reduced magnitude of overall loses after implementation of DG. Base from the amount of losses in both the cases, we found that the system performed better when DG is implemented.

Table 1

Losses obtained by Gauss-Seidel calculation method for the system.

Table 2

Output data from PSSE for the system without DG.

Table 3

Output data from PSSE for the system with DG.

Appendix A

Table A.1

Network data used for calculations.

References

  1. M. Kumar, A. Kumar, K.S. Sandhu, PV-WT based distribution generator location minimizing transmission loss in Pool/Bilateral electricity market model, Procedia Technol. 25, 692–701 (2016) [CrossRef] [Google Scholar]
  2. T.L. Alumona et al., Overview of Losses and Solutions in Power Transmission Lines (2014) Vol. 4 [Google Scholar]
  3. International Agency for research on 2015 cancer, IARC monograph on evaluation of carcinogenic risk to human, Vol. 80, part 1. [Google Scholar]
  4. R. Jimenz, T. Serrisky, K. Mercado, Power Lost: Sizing Electricity Loses in Transmission and Distribution System in Latin America and Caribbean, 2014 [CrossRef] [Google Scholar]
  5. J. Parmar, Total Losses in Power Distribution and Transmission Lines-Part 1 (2013) https://electricalnotes.wordpress.com [Google Scholar]
  6. J.B. Gupta, in Switch Gear and Protection, 2nd edn. (SK Kataria and Sons, New Delhi, 2004) pp. 29–608 [Google Scholar]
  7. H.A. Attia, Z.H. Osman, M. El-Shibini, A.A. Moftah, An assessment of distributed generation impacts on distribution networks using global performance index, Nat. Sci. 8, 150–158 (2010) [Google Scholar]
  8. C.T. Borges, D.M. Falcao, Impact of distributed generation allocation and sizing on reliability, losses and voltage profile, in IEEE Bologna Power Tech, Conference Bologna (Italy, 2003), pp. 1–5 [Google Scholar]
  9. T. Ackermann, G. Andersson, L. Soder, Distributed generation: a definition, Electr. Power Syst. Res. 57, 195–204 (2001) [CrossRef] [Google Scholar]
  10. C.J. Mozina, A Tutorial on the Impact of Distributed Generation (DG) on Distribution Systems (2010) p 19. [Google Scholar]
  11. A.S.O. Ogunjuyigbe, T.R. Ayodele, O.O. Akinola, Impact of distributed generators on the power loss and voltage profile of sub-transmission network, J. Electr. Syst. Inf. Technol. 3, 94–107 (2016) [Google Scholar]
  12. C.L. Wadhwa, in Electrical Power System, 4th edn. Chapter 18 (New Age International, Chennai, 2005) [Google Scholar]
  13. P. Cunningham, I. Woofenden, Micro-hydro electric system, Home power 117, (2007) Viewed on 2016/08, https://www.homepower.com [Google Scholar]
  14. IEEE Standard for Interconnecting Distributed Resources with Electric Power Systems Standards Coordinating Committee 21, Sponsor by (Fuel Cells, Photovoltaics, Dispersed Generation, and Energy Storage), Approved 2003/12/06, Reaffirmed 2008/25/09 [Google Scholar]
  15. T.J. Coutts, An overview of thermophotovoltaic generation of electricity, NREL/CP-520- 26904, in 11th International Photovoltaics Science and Engineering Conference (PVSEC-11) (1999) [Google Scholar]

Cite this article as: Chaantrea Miky Lamin, Arvind Kumar Singh, Minimization of transmission loss using distributed generation approach, Int. J. Simul. Multidisci. Des. Optim. 9, A1 (2018)

All Tables

Table 1

Losses obtained by Gauss-Seidel calculation method for the system.

Table 2

Output data from PSSE for the system without DG.

Table 3

Output data from PSSE for the system with DG.

Table A.1

Network data used for calculations.

All Figures

thumbnail Fig. 2

Single line diagram of the system parameters after implementation of DG.

In the text
thumbnail Fig. 1

Single line diagram of actual parameter of the network without DG.

In the text

Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.

Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.

Initial download of the metrics may take a while.